GATE EE 2024 — Question 40

Electrical MachinesSynchronous machines: cylindrical and salient pole machines, performance and characteristics, regulation and parallel operation of generators, starting of synchronous motorsMCQ2 marks · −2/3 if wrongMedium

A 3-phase, 11 kV, 10 MVA synchronous generator is connected to an inductive load of power factor \((\sqrt{3}/2)\) via a lossless line with a per-phase inductive reactance of 5 Ω. The per-phase synchronous reactance of the generator is 30 Ω with negligible armature resistance. If the generator is producing the rated current at the rated voltage, then the power factor at the terminal of the generator is
  1. A
    0.63 lagging.
  2. B
    0.87 lagging.
  3. C
    0.63 leading.
  4. D
    0.87 leading.