A 3-phase, 11 kV, 10 MVA synchronous generator is connected to an inductive load of power factor via a lossless line with a per-phase inductive reactance of 5 Ω. The per-phase synchronous reactance of the generator is 30 Ω with negligible armature resistance. If the generator is producing the rated current at the rated voltage, then the power factor at the terminal of the generator is
- A0.63 lagging.
- B0.87 lagging.
- C0.63 leading.
- D0.87 leading.