For the three-bus power system shown in the figure, the trip signals to the circuit breakers B to B are provided by overcurrent relays R to R, respectively, some of which have directional properties also. The necessary condition for the system to be protected for short circuit fault at any part of the system between bus 1 and the R-L loads with isolation of minimum portion of the network using minimum number of directional relays is


- AR and R are directional overcurrent relays blocking faults towards bus 2
- BR and R are directional overcurrent relays blocking faults towards bus 2 and R is directional overcurrent relay blocking faults towards bus 3
- CR and R are directional overcurrent relays blocking faults towards Line 1 and Line 2, respectively, R is directional overcurrent relay blocking faults towards Line 3 and R is directional overcurrent relay blocking faults towards bus 2
- DR and R are directional overcurrent relays blocking faults towards Line 1 and Line 2, respectively.