GATE EE 2023 — Question 20

Power SystemsCircuit breakersMCQ1 mark · −1/3 if wrongMedium

For the three-bus power system shown in the figure, the trip signals to the circuit breakers B\(_1\) to B\(_9\) are provided by overcurrent relays R\(_1\) to R\(_9\), respectively, some of which have directional properties also. The necessary condition for the system to be protected for short circuit fault at any part of the system between bus 1 and the R-L loads with isolation of minimum portion of the network using minimum number of directional relays is
Question image
  1. A
    R\(_3\) and R\(_4\) are directional overcurrent relays blocking faults towards bus 2
  2. B
    R\(_3\) and R\(_4\) are directional overcurrent relays blocking faults towards bus 2 and R\(_7\) is directional overcurrent relay blocking faults towards bus 3
  3. C
    R\(_3\) and R\(_4\) are directional overcurrent relays blocking faults towards Line 1 and Line 2, respectively, R\(_7\) is directional overcurrent relay blocking faults towards Line 3 and R\(_5\) is directional overcurrent relay blocking faults towards bus 2
  4. D
    R\(_3\) and R\(_4\) are directional overcurrent relays blocking faults towards Line 1 and Line 2, respectively.