Power SystemsEconomic Load Dispatch (with and without considering transmission losses)MCQ1 mark · −1/3 if wrongMedium

The expressions of fuel cost of two thermal generating units as a function of the respective power generation \(P_{G1}\) and \(P_{G2}\) are given as \(F_1(P_{G1}) = 0.1aP_{G1}^2 + 40\,P_{G1} + 120\ Rs/hour \qquad 0\ MW \le P_{G1} \le 350\ MW\) \(F_2(P_{G2}) = 0.2P_{G2}^2 + 30\,P_{G2} + 100\ Rs/hour \qquad 0\ MW \le P_{G2} \le 300\ MW\) where \(a\) is a constant. For a given value of \(a\), optimal dispatch requires the total load of 290 MW to be shared as \(P_{G1} = 175\ MW\) and \(P_{G2} = 115\ MW\). With the load remaining unchanged, the value of \(a\) is increased by 10% and optimal dispatch is carried out. The changes in \(P_{G1}\) and the total cost of generation, \(F\) (= \(F_1 + F_2\)) in Rs/hour will be as follows
  1. A
    \(P_{G1}\) will decrease and \(F\) will increase
  2. B
    Both \(P_{G1}\) and \(F\) will increase
  3. C
    \(P_{G1}\) will increase and \(F\) will decrease
  4. D
    Both \(P_{G1}\) and \(F\) will decrease